MECHANICAL
Riser:
Conductor: Bare Copper Wire 23AWG
Cable diameter - in. (mm): 0.23 (5.8) Nom.
Nominal weight 1000ft reel - lbs. (kg): 34.9 (15.83)
Nominal cable weight - lb./kft. (kg/km): 26 (38)
Maximum installation tension - lb. (N): 25 (110)
Minimum bend radius - in. (mm): ≥ 4 O.D @-20° C / -4°F
Insulation: Polyethylene
Plenum
Conductor: Bare Copper Wire 23AWG
Cable diameter - in. (mm): 0.23 (5.8) Nom.
Nominal weight 1000ft reel - lb. (kg): 29.6 (13.44)
Nominal cable weight - lb./kft. (kg/km): 26 (38)
Maximum installation tension - lb. (N): 25 (110)
Minimum bend radius: ≥ 4 O.D @-20° C / -4°F
Operating Temperature: 14°F to +140°F (-10°C to 60°C)
ELECTRICAL
Mutual Capacitance: 5.6nF/100 m nom.
DC Resistance Maximum: 9.38 Ω/100 m maximum
Skew: 45 ns/100 m maximum
Pair to Ground Unbalance:
Plenum - 330 pF/100 m maximum
Riser - 160 pF/100m maximum
Nominal Velocity of Propagation (NVP): 67% Nom
COMMERCIAL STANDARDS
ANSI/TIA-568.2-D and ISO/IEC 11801
PoE: IEEE 802.3bt-2018
UL, CSA approved. File no E316962
FIRE PROPAGATION TESTS
CMP and CMR Listed
ENVIRONMENTAL
RoHS Compliant
PoE
Our PowerCat 6 system is suitable for PoE applications as defined below:
IEEE 802.3bt from Type 1 to Type 4, and CISCO UPoE+
Notes: For new installations of PoE Type 3 / Class 5 and above that wish to be eligible for the Molex 25 year Application Assurance Warranty, we require Category 6A cable to be used throughout.
To confirm your PoE / RP3 cabling design is eligible for the Molex 25 year Application Assurance Warranty, your design must be verified and validated with the Molex PoE Calculator. Read more https://www.molexces.com/poe-calculator Molex recommends that the PoE feature on an individual switch port are power disabled prior to unplugging the associated powered Device.
Molex recommends that the full range of PowerCat 6 products be used in a system to maximize cabling and PoE performance Details on Molex requirements for Warranty can be found at https://www.molexces.com/about-us/our-warranty/